AI Data Center
An AI data center, often called an AI factory, is a facility built to train and run AI models at scale. It takes in data and power and produces trained models and inference output. Its design is driven by dense GPU compute, very fast networks between GPUs, high-throughput storage, and power and cooling far beyond a conventional data center.
How it differs from a traditional data center
| Area | Traditional data center | AI data center |
|---|---|---|
| Rack power | About 5 to 15 kW per rack | About 40 to 140 kW per rack today, with vendor roadmaps well beyond that |
| Cooling | Air cooling with CRAC or CRAH units | Direct-to-chip liquid cooling, rear-door heat exchangers, or both |
| Network | Mostly north-south traffic, 10/25/100G | Heavy east-west GPU traffic on a lossless 400G or 800G fabric |
| Storage | Block and file storage for applications | Parallel file systems and all-flash NVMe sized for throughput |
| Workload | Many independent applications | Large training jobs and inference services that use many GPUs as one system |
| Floor loading | Standard raised floor | Much heavier racks, often on slab, with liquid piping |
Building blocks
1. Compute
- GPU nodes: servers with multiple accelerators, or rack-scale systems where a whole rack is designed, cabled and cooled as one unit.
- CPU nodes: head nodes, login nodes, schedulers, data preparation and general services.
- DPUs and SmartNICs: offload networking, storage and security functions, and isolate tenants.
- Scalable unit (pod): a repeatable block of GPU racks with its network and storage. Capacity grows by adding pods.
2. Networking
An AI data center has four separate networks. Keep them separate in the design.
- Back-end (GPU) fabric: east-west traffic between GPUs for training. InfiniBand or lossless Ethernet with RoCEv2, 400G or 800G, in a non-blocking leaf-spine (fat-tree) or rail-optimized layout.
- Front-end network: user access, inference traffic, data ingest and connection to the rest of the enterprise. Usually Ethernet with EVPN-VXLAN.
- Storage network: a dedicated high-speed path between compute and storage. It is sometimes combined with the front-end network in smaller builds.
- Out-of-band management: BMC, console, PDU, CDU and switch management on an isolated network.
Points to design for: 1:1 subscription on the GPU fabric, congestion control (PFC and ECN for RoCE), optics and cable planning (DAC, AOC, transceivers, fiber counts), and IP addressing for every network.
3. Storage
- High-performance tier: parallel file system or scale-out all-flash NVMe for training data and checkpoints.
- Capacity tier: object storage for datasets, model archives and logs.
- Local NVMe: scratch and cache on GPU nodes.
- Sizing inputs: dataset size, read throughput per GPU, checkpoint size and frequency, and retention.
4. Power
- Utility and capacity: AI halls are planned in megawatts. Grid availability and lead time often decide the site.
- Distribution: transformers, switchgear, UPS, busway and high-capacity rack PDUs or power shelves. Higher-voltage DC distribution is emerging for very dense racks.
- Redundancy: choose N, N+1 or 2N per load type. Training clusters are sometimes run at lower redundancy than inference.
- Backup: UPS, batteries and generators sized for the load profile. GPU load can swing sharply during training.
- Efficiency: track PUE and power per rack from day one.
5. Cooling
- Direct-to-chip liquid cooling: cold plates on GPUs and CPUs remove most of the heat.
- Coolant distribution units (CDUs): in-rack or in-row units that separate the facility water loop from the technology cooling loop.
- Residual air cooling: liquid-cooled racks still give off some heat to air, so rear-door heat exchangers or room cooling are still needed.
- Heat rejection: chillers, dry coolers or cooling towers, depending on climate and water availability.
- Points to design for: supply temperature, flow rate, water quality, leak detection, redundancy of pumps and CDUs, and maintenance access.
6. Facility and space
- Floor loading for racks that can weigh well over a tonne.
- Rack layout that keeps GPU fabric cable lengths within limits.
- Overhead or underfloor routes for power, liquid piping and fiber.
- Fire detection and suppression suited to liquid-cooled halls.
- Physical security, access control and monitoring.
7. Software and operations
- Cluster management: provisioning, firmware and driver lifecycle for GPU nodes.
- Scheduling: Slurm for batch training, Kubernetes for inference and services, or both.
- MLOps platform: data pipelines, experiment tracking, model registry and model serving.
- Monitoring: GPU utilization, job efficiency, fabric health, power, coolant temperature and flow, with DCIM and BMS integration.
8. Security and governance
- Tenant isolation across compute, network and storage.
- Zero Trust access for users, administrators and APIs.
- Protection of training data, model weights and prompts.
- Segmentation between front-end, back-end, storage and management networks.
- Logging, audit and compliance with data residency rules.
Training and inference need different designs
| Area | Training | Inference |
|---|---|---|
| Goal | Finish large jobs fast | Low latency and high availability |
| GPU fabric | Critical, non-blocking | Less critical for most models |
| Storage | Very high read throughput and checkpointing | Fast model loading, modest throughput |
| Redundancy | Can restart from a checkpoint | Needs redundancy like any production service |
| Location | Central, where power is available | Central or close to users |
Design sequence
- Define workloads: training, fine-tuning, inference, model sizes and number of users.
- Size compute: number and type of GPUs, and the scalable unit.
- Derive power and cooling load per rack and per hall.
- Confirm site capacity: utility power, cooling water, floor loading and space.
- Design the four networks and the cabling plan.
- Size storage tiers.
- Define the software stack, security controls and operating model.
- Produce the HLD, LLD and BoQ.
- Plan implementation: rack and stack, liquid loop commissioning, fabric validation, burn-in and acceptance tests.
Planning checklist
- Workload profile and growth forecast for three to five years
- Power per rack, total IT load and redundancy level
- Cooling method, CDU capacity and facility water readiness
- GPU fabric topology, subscription ratio and optics count
- Front-end, storage and management network design
- Storage throughput and capacity per tier
- Floor loading, rack layout and cable routes
- Scheduler, MLOps and monitoring tools
- Security, tenant isolation and compliance requirements
- Delivery lead times for GPUs, optics, switchgear and cooling equipment
- Acceptance tests and performance benchmarks
Key terms
- AI factory: a data center built to produce AI models and inference output at scale.
- Pod or scalable unit: a repeatable block of GPU racks, network and storage.
- Back-end fabric: the dedicated network that connects GPUs to each other.
- RoCEv2: RDMA over Converged Ethernet, used for low-latency GPU traffic on Ethernet.
- Rail-optimized design: each GPU position in a node connects to its own leaf switch to shorten paths.
- DLC: direct-to-chip liquid cooling.
- CDU: coolant distribution unit.
- PUE: power usage effectiveness, total facility power divided by IT power.
- DPU: data processing unit, a network card with its own processor.
The figures on this page are typical ranges. Confirm exact values with the reference design of the platform you select.
Industry news
Latest AI Data Center headlines
- HPCwire · 23 Nov 2026Clemson’s 2nd Annual HPC Day Draws More Than 260 Attendees
- HPCwire · 23 Nov 2026Germany’s planqc Forms UK Subsidiary, Plans Cambridge Lab for Neutral-Atom Quantum Computing
- The Next Platform · 23 Nov 2026Jensen Huang Back In Charge Of Nvidia
- The Next Platform · 21 Nov 2026The Storm Is Over, but Costs Keep Coming: How Utilities Can Strengthen Financial Oversight Throughout a Storm Response
- AIwire · 20 Nov 2026Valkey Releases Version 9.2 Alongside Distributed KV Caching for AI Inference
- AIwire · 20 Nov 2026Mirantis Joins Lenovo AI Innovators to Help Cloud Providers Turn GPU Infrastructure into AI Services
- NVIDIA Developer · 19 Nov 2026Reducing Rollout Bottlenecks in Reinforcement Learning with NVIDIA Dynamo
- NVIDIA · 19 Nov 2026NVIDIA and Microsoft Expand Accelerated Computing From Azure to Windows PCs